Progressive Horizontal Evacuation and Fire Suppression: What Should Care Home Project Teams Coordinate?
Progressive horizontal evacuation and automatic fire suppression need to be coordinated as parts of the same care home fire-safety strategy. Suppression can help control fire growth, but the building still relies on protected areas, compartmentation, doors, detection, staff response and resident-specific evacuation arrangements. The project team should agree how these measures work together before the sprinkler or water mist design is fixed.
NPHS supports care home operators, developers, consultants and contractors with sprinkler, water mist and specialist fire suppression design coordination, installation, commissioning, documentation and planned maintenance.
What is progressive horizontal evacuation in a care home?
Progressive horizontal evacuation, often shortened to PHE, is an evacuation approach commonly used in care homes where some residents may need staff assistance to move safely. People are moved away from the fire into an adjoining protected area on the same storey before any further evacuation is considered.
Home Office guidance for residential care premises describes progressive horizontal evacuation as a strategy likely to be necessary where residents depend on staff assistance. It works by moving residents from the fire-affected area through a fire-resisting barrier into an adjoining protected area on the same level, with further evacuation considered if needed.
That makes the relationship between compartmentation, protected areas, resident dependency and staff numbers central to the fire strategy. Automatic suppression can support that strategy by controlling fire growth, but it does not replace the need for the evacuation arrangement itself.

Why does suppression need to be coordinated with the evacuation strategy?
A care home fire suppression system is only one layer of protection. The evacuation strategy relies on people being able to move from the affected area into a place of relative safety while staff manage residents with different mobility, cognitive and care needs.
If the suppression system is designed without understanding the protected areas, compartment boundaries or evacuation assumptions, the project can end up with technical documents that do not tell the same story. The fire strategy might assume one arrangement while the suppression drawings, ceiling plans and maintenance access have been developed around another.
Early coordination gives the project team a chance to align the fire strategy, architectural design, M&E coordination, suppression coverage and operational plan before ceilings close or residents occupy the building.
What should the project team coordinate?
| Coordination point | Why it matters | Who normally needs input |
|---|---|---|
| Protected areas and compartment lines | PHE relies on moving residents into adjoining protected areas separated by fire-resisting construction. | Architect, fire consultant, care operator, suppression designer |
| Resident dependency | Mobility, cognition and care needs affect how quickly residents can be moved and how much staff assistance may be required. | Care operator, fire risk assessor, fire consultant |
| Sprinkler or mist coverage | The suppression design should match the agreed fire strategy, standard and protected areas. | Suppression designer, fire consultant, M&E consultant |
| Ceiling and service coordination | Nozzles or sprinkler heads must remain correctly positioned around lights, detectors, ventilation and ceiling features. | Suppression designer, M&E team, architect |
| Alarm and control interfaces | Suppression, detection and building controls may need defined cause-and-effect relationships. | Fire alarm contractor, M&E team, suppression contractor |
| Maintenance access | Pumps, valves, tanks, controls and test points need to remain accessible once the home is operational. | Care operator, facilities team, suppression contractor |
Are sprinklers required in new care homes in England?
For new care homes in England, the 2025 amendment to Approved Document B took effect on 2 March 2025, subject to transitional provisions. It states that care homes should be fitted with a sprinkler system throughout the building in accordance with Appendix E.
The same amendment also changed other care-home provisions, including a 10-bed limit for protected areas and requirements for self-closing devices on doors. These measures reinforce the need to coordinate suppression with the wider evacuation and compartmentation strategy.
This guidance is specific to England. Scotland, Wales and Northern Ireland have their own building standards or regulations, so the compliance route should be confirmed for the project location.
Care Home Fire Suppression Systems
Which sprinkler standard may apply to a care home?
BSI lists BS 9251:2021 as the current code of practice for fire sprinkler systems in domestic and residential occupancies. It covers design, installation, water supplies, commissioning, maintenance and testing for life-safety sprinkler systems within its scope.
The correct BS 9251 system category depends on the building and risk. Care premises with greater resident numbers or higher-risk characteristics can require a different category from a small domestic building, with consequences for water supply, pump resilience and system performance.
The category should be confirmed from the current standard and project information rather than copied from a previous care-home specification.
How does BS 9991:2024 affect care home projects?
BS 9991:2024 includes care homes within its scope. BSI also states that the current edition refers solely to sprinkler systems in its fixed firefighting recommendations.
That matters for older specifications. A project document that refers to BS 9991 and water mist as though the current standard gives both systems the same fixed-firefighting route needs review.
Where BS 9991 forms part of the residential fire-safety strategy, the design team should check the current edition and make sure the suppression specification is consistent with it.
BS 9991 Water Mist & Sprinkler Systems
Can water mist still be considered in a care home?
Water mist can be considered for some care and supported-living projects where the system is suitable for the risk and is supported by the appropriate standards, fire-test evidence and project-specific approval route.
Older care-home specifications may still refer to BS 8458:2015, which BSI withdrew in 2025. Current water mist proposals should be reviewed against the relevant BS EN 14972 framework, applicable fire-test evidence and the project-specific approval route. Existing evidence associated with BS 8458 should be considered on its project-specific merits rather than assumed to be automatically invalid.
Where Approved Document B or BS 9991 specifically points to sprinklers, a water mist proposal should not be presented as automatically equivalent. The fire consultant, Building Control body and other relevant stakeholders should consider the project-specific technical route and supporting evidence.
BS EN 14972 Water Mist Systems
How should resident dependency affect the suppression design conversation?
Resident dependency affects the amount of time and staff support needed to move people from the fire area. Some residents may walk independently. Others may need physical assistance, specialist equipment or a more carefully managed transfer into the next protected area.
The suppression designer does not set the care home evacuation policy, but they need enough information to understand the building use and agreed strategy. A fire system designed for an abstract floor plan without the operational context can miss important coordination issues.
The care operator and fire consultant should therefore make the resident profile and evacuation assumptions clear enough for the suppression package to be designed around the real building use.
Why do compartmentation and suppression need separate attention?
Progressive horizontal evacuation depends on fire-resisting construction between protected areas. Automatic suppression can help control a developing fire, but it should not be used as a reason to ignore damaged compartment lines, unsuitable doors or unsealed service penetrations unless the accepted design route explicitly allows a particular variation.
On refurbishment projects, the suppression survey can also expose coordination risks. Pipe routes may cross compartment walls or floors, which means penetrations need appropriate fire stopping and documentation.
For care home operators, this is useful at handover because the final records should show both where the suppression system runs and how the associated fire-resisting construction has been maintained around the installation.
What should happen at design stage?
At design stage, the project team should confirm the fire strategy, building type, resident profile, evacuation approach, proposed suppression system, relevant standard and water-supply route.
The suppression specialist can then coordinate plant space, tanks, pumps, risers, pipework, head or nozzle positions, controls and maintenance access. That information should be shared with the architect and M&E team early enough to influence the design.
The aim is to avoid a late-stage clash where the plant room is too small, a ceiling raft blocks coverage, a valve is hidden above fixed joinery or the fire strategy has changed without the suppression design being updated.
How should live care homes plan retrofit work?
Existing care homes need a different delivery plan from new-build projects because residents and staff may remain in occupation throughout the works.
A retrofit programme should account for room access, noise, dust, ceiling opening, resident safeguarding, staff routines and temporary restrictions. The contractor also needs to understand which areas can be worked in at the same time without undermining the home's operational fire-safety arrangements.
Phasing by wing, floor or protected area can make the project easier to manage, provided the commissioning and temporary arrangements are clearly controlled.
How should detection and alarm interfaces be coordinated?
Care home suppression does not operate in isolation from detection and alarm systems. The project may need defined interfaces for alarms, pump status, valve monitoring, plant controls or other cause-and-effect functions.
Those interfaces should be agreed before commissioning. Otherwise, the fire alarm contractor and suppression contractor can each complete their own package while the combined cause-and-effect remains unclear.
The handover information should identify the relevant interfaces so the care operator and future maintenance teams know which system generates each signal and what action is expected.
What should be included in care home commissioning and handover?
Commissioning should confirm that the installed suppression system reflects the agreed design and applicable standard. The exact tests depend on the system type and project route.
The care home operator should receive clear system drawings, commissioning records, plant and valve information, operating guidance, maintenance requirements and records of any outstanding items. If installation is phased, the documents should make clear which areas are complete and operational.
This documentation matters because care settings often have staff changes, external audits and multiple contractors working on the building over its lifetime. Future teams need to understand what was installed without reconstructing the project history from old emails.
How should maintenance support the evacuation strategy?
A suppression system that is difficult to inspect or poorly documented can undermine the confidence the care operator places in it. Maintenance access should therefore be planned before the building is handed over.
Pumps, tanks, valves, controls, test points, nozzles and sprinkler heads need to remain accessible. Refurbishment work should also trigger a review where ceilings, bedrooms, corridors, compartment lines or service routes change.
NPHS can provide planned inspection, servicing, defect reporting and maintenance records for care home sprinkler, water mist and wider fire suppression systems.
Fire Suppression System Maintenance
Fire Sprinkler Maintenance & Inspection
What should care home project teams confirm before tender?
Before the suppression package is priced, the tender information should make the required scope and technical route clear enough for bidders to price the same job.
| Tender item | What should be clear |
|---|---|
| Fire strategy | Current revision, evacuation strategy and relevant assumptions |
| Building and resident use | Care type, number of residents, protected areas and operational constraints |
| Suppression route | Sprinkler, water mist or other accepted route, with relevant standard |
| Coverage | Which bedrooms, corridors, ancillary spaces and other areas require protection |
| Water supply and plant | Known mains information, storage, pump and plant-space assumptions |
| Interfaces | Fire alarm, monitoring, controls and any shutdown functions |
| Occupied-building constraints | Access, working hours, safeguarding and phasing requirements |
| Handover and maintenance | Commissioning records, drawings, maintenance information and service access |
What information should you send NPHS?
Send the latest drawings and fire strategy first. If the home is already operating, include any current fire risk assessment, maintenance records and information about resident occupancy or areas that are difficult to access.
- Building drawings and protected-area layout
- Fire strategy and evacuation approach
- Care home type, resident profile and number of beds
- Existing or proposed sprinkler, water mist or suppression information
- Water-supply and plant-space information where available
- Building Control, consultant or insurer comments
- Programme and occupancy constraints for live buildings
NPHS can then review the practical suppression requirements and identify the information still needed before design, quotation or installation.
Need help coordinating fire suppression on a care home project?
NPHS supports care home operators, developers, housing providers, architects, consultants and contractors with sprinkler, water mist and specialist fire suppression projects across the UK.
We can review the fire strategy and drawings, advise on the suppression route, coordinate installation requirements, commission the system and provide planned maintenance after handover.
Frequently asked questions
What is progressive horizontal evacuation in a care home?
Progressive horizontal evacuation moves residents away from the fire into an adjoining protected area on the same storey before further evacuation is considered. It is commonly used where residents may need staff assistance and depends on compartmentation, protected areas, staffing and a clear operational plan.
Do new care homes in England need sprinklers?
Approved Document B guidance effective from 2 March 2025 states that care homes should be fitted with a sprinkler system throughout the building, subject to the detailed guidance and transitional provisions. The position should be checked against the project date, location and Building Control route.
Can water mist be used in a care home?
Water mist can be considered on some projects where it suits the risk and is supported by the relevant BS EN 14972 requirements, fire-test evidence and project-specific approval route. It should not be assumed to be automatically equivalent where the applicable guidance or fire strategy specifically requires sprinklers.
How does fire suppression support progressive horizontal evacuation?
Automatic suppression can help control fire growth and reduce heat release while staff move residents into an adjoining protected area. It remains one part of the wider strategy alongside compartmentation, doors, detection, staff procedures and resident-specific evacuation planning.
Can NPHS work in an occupied care home?
Yes. NPHS can support retrofit and maintenance work in occupied care settings, subject to survey and planning. The programme can account for resident safeguarding, room access, working hours, ceiling routes, commissioning and future maintenance access.
Need help coordinating fire suppression on a care home project?
NPHS supports care home operators, developers, housing providers, architects, consultants and contractors with sprinkler, water mist and specialist fire suppression projects across the UK.
Send us the fire strategy, drawings, evacuation approach and any Building Control or consultant comments. We can review the suppression route, standards, water supply, plant space, installation constraints, commissioning requirements and long-term maintenance needs.
Send your care home drawings and fire strategy for review
Primary sources
GOV.UK: Approved Document B, Volume 2: Buildings other than dwellings
GOV.UK: Fire safety risk assessment: residential care premises